Quick Answer: Power Connection and BMS Communication Are Different
When several battery packs operate in parallel, connecting them on the DC power side does not automatically connect their BMS units on the communication side.
For the DALY 4th Gen Home Energy Storage BMS architecture covered here, the practical communication path is: Each Pack → Its BMS → Automatic BMS Identification → Internal RS485 → Main/Host Communication Point → Inverter Communication.
The customer therefore needs to verify three things separately: each pack has the correct BMS, the BMS units can be identified and linked internally, and the battery system uses the interface and protocol required by the exact inverter.
Key point: Electrical parallel connection ≠ BMS communication ≠ inverter communication.
1. Each Battery Pack Still Has Its Own BMS
In a multi-pack battery bank, each battery pack is managed by its own BMS. The BMS monitors and protects that individual pack before the packs participate in the larger energy storage system.
| Battery pack | Pack-level BMS |
|---|---|
| Pack 1 | BMS 1 |
| Pack 2 | BMS 2 |
| Pack 3 | BMS 3 |
| … | … |
| Pack n | BMS n |
This means the power architecture and the communication architecture should be checked separately. A common DC connection does not create a BMS communication network by itself.
2. Make Sure Every BMS Can Be Identified
Once several BMS units share one multi-pack system, the system needs a reliable way to distinguish one BMS from another.
In the supported DALY 4th Gen parallel architecture, automatic BMS address identification reduces the need for manual DIP-switch address configuration during commissioning.
Customer check: Can the system identify each BMS correctly before you continue to inverter communication?
BMS identification solves the device-identification step. It does not, by itself, confirm inverter compatibility.
3. Connect the BMS Units Through the Internal Communication Layer
For the DALY 4th Gen architecture covered by the available product materials, internal communication between parallel-pack BMS units uses RS485 in a daisy-chain arrangement.
A simplified communication path is: Pack 1 / BMS 1 → Pack 2 / BMS 2 → Pack 3 / BMS 3 → … → Pack n / BMS n.
This RS485 communication path is different from the main DC power connection between the battery packs.
Actual connector pin definitions, cable sequence, termination, and commissioning procedures should follow the applicable DALY product documentation.
4. Separate Internal BMS Communication From Inverter Communication
| Communication link | Purpose | DALY 4th Gen architecture covered here |
|---|---|---|
| BMS ↔ BMS | Identify and connect BMS units inside the parallel battery system | Internal RS485 |
| Battery system ↔ Inverter | Exchange battery information with a compatible inverter | CAN / RS485 with the applicable supported protocol |
A CAN or RS485 interface alone does not establish inverter compatibility. The exact inverter model and required communication protocol must also match the selected BMS configuration.
Customer rule: Interface compatibility and protocol compatibility are separate checks.
5. Multi-Pack Communication Commissioning Checklist
| Check | What to confirm |
|---|---|
| Pack architecture | How many battery packs will operate in parallel? |
| Pack-level BMS | Is each pack using the required BMS configuration? |
| BMS identification | Can every BMS be identified correctly? |
| Internal communication | Is the BMS-to-BMS RS485 communication path established? |
| Communication topology | Are the BMS units linked according to the applicable product documentation? |
| Main/host communication point | Which battery/BMS connection communicates toward the inverter? |
| Inverter model | What is the exact brand and model? |
| Interface | Does the project require CAN or RS485? |
| Protocol | Does the selected BMS configuration support the required inverter protocol? |
Complete these checks before treating the parallel battery bank as an integrated BMS communication system.
6. What Does DALY 4th Gen Support for This Architecture?
| Function | Supported capability |
|---|---|
| Parallel expansion | Up to 16 PACKs in the supported configuration |
| BMS identification | Automatic BMS address identification |
| Internal multi-pack communication | RS485 |
| Multi-pack visibility | Individual pack information can be viewed in supported monitoring interfaces |
| Inverter-facing communication | CAN / RS485 with supported inverter protocols |
For supported monitoring configurations, individual pack information can include pack number, operating state, voltage, current, SOC, charge MOS status, and discharge MOS status.
This article stops at communication topology: who is identified, how the BMS units are linked, and how the battery system reaches the inverter interface.
Next integration question: If you need to determine what multi-pack battery data the inverter receives—such as SOC, current, alarms, or other system-level information—verify the system-data behavior separately for the applicable BMS configuration and inverter protocol.
FAQ
Does each parallel battery pack need its own BMS?
In the multi-pack architecture discussed here, yes: each battery pack is managed by its own BMS, while the communication architecture links the BMS units at system level.
Does DALY 4th Gen use RS485 between parallel packs?
In the DALY 4th Gen architecture covered here, internal parallel-pack BMS communication uses RS485. Do not generalize this to every DALY product or every energy storage architecture.
If both the BMS and inverter have CAN, are they compatible?
Not automatically. The physical interface, exact inverter model, communication protocol, and selected BMS configuration must be checked together.
Request a Parallel BMS Communication Review
For a multi-pack energy storage project, send DALY your battery chemistry, S count, capacity per pack, number of parallel packs, BMS current requirement, exact inverter brand/model, required CAN/RS485 interface, communication protocol, monitoring requirement, and expected quantity.
This allows the technical team to verify the communication architecture before sample testing or commissioning.